亚洲精品免费日日日夜夜夜夜,国产一区二区在线视频,日韩高清一区二区三区五区七区,特级毛片aaaa免费观看,亚洲视频一区在线观看

            Noise control project of China telecom channel communication hub New York center

            Column:Industrial noise control Time:2018-11-19
            shared:

            image.png


            Project description: the noise reduction project of the auxiliary energy center room of China telecom channel communication hub building is located in xiamen channel communication hub center. The noise generated by the 8 × 2400KW diesel generator set in the energy center room during operation reaches about 105 db, which has a great impact on the nearby environment. According to the operation characteristics of the generator set, our company effectively reduces the noise of the generator set and the generator room, and reduces the noise level inside and outside the room while ensuring the normal operation of the generator set. The impedance muffler is used to reduce the sound pressure level and sound energy of the inlet and outlet of the generator set on the premise of ensuring the air inlet and outlet of the generator set. The indoor environment for sound absorption processing, reduce the indoor reverberation sound. After noise reduction processing, factory boundary noise can meet the discharge standard of environmental noise within the boundary of industrial enterprises "(GB12348-2008) Ⅱ class area standards; Namely, daytime ≤60dB (A) and night ≤50dB (A).


            Treatment measures: install sound-absorbing wall in the wall of the generator room, effectively absorb and isolate noise, reduce indoor reverberation sound, the total area is 478 square meters, the wall height is 6.3 meters. The lower part of the floor is installed with a sound-absorbing ceiling to effectively absorb and isolate noise and reduce indoor reverberation. The installation height is 6.3 meters and the total area is 263 square meters.


            Generator running flow of air through into the wind channel into the generator room, in order to prevent noise from intake channel opening spread outward, in both internal and external intake channel installation into the exhaust muffler, into the exhaust muffler with resistance, resistance and noise elimination principle designed muffler structure, has high ability of noise elimination of 25 db (A) above.